EVT-RM-P SERIES

EVT-RM-P SERIES

RACKMOUNT UPS PROFESSIONAL SERIES

  • Rackmount Design for Rack Cabinet Applications
  • High Frequency On-line Double-conversion Tech.
  • Comprehensive Display for Easy monitoring & UPS Status
  • ECO Mode for Energy Saving (Only for 1-3kVA Models)
  • Generator compatible

Download Datasheet

Category:

Description

MODEL EVT-RM1KV-P EVT-RM2KV-P EVT-RM3KV-P EVT-RM5KV-P EVT-RM10KV-P
Phase Single phase with ground
Capacity 1000 VA / 900 W 2000 VA / 1800 W 3000 VA / 2700 W 5000 VA / 4500 W 10000 VA / 9000 W
INPUT
Nominal voltage 110/115/120/127VAC or 208/220/230/240VAC 208/220/230/240VAC
Input voltage range 60-145 VAC or 120-300 VAC at 50% load, 90-145 VAC or 180-300 VAC at 100% load 110-300 VAC (Based on load at 50%), 176-300 VAC (Based on load at 100%)
Frequency range 40Hz ~ 70 Hz
Power factor _ 0.99 @ Nominal Voltage (100% load)
Bypass voltage range − 25% ~ +15% (settable) – 40% ~ +15% (settable)
Total harmonic distortion (THDi) ≤ 6% ≤ 5%
OUTPUT
Voltage 110/115/120/127VAC or 208/220/230/240VAC 208/220/230/240VAC
Voltage regulation ± 1%
Frequency range 47~ 53Hz or 57 ~ 63Hz (synchronized range) 46Hz ~ 54Hz or 56Hz ~ 64Hz (synchronized range)
50Hz ± 0.25Hz or 60Hz ± 0.3Hz (battery mode) 50Hz ± 0.1Hz or 60Hz ± 0.1Hz (battery mode)
Waveform (Batt. Mode) Pure Sinewave
Power factor 0.8 0.9
Total harmonic distortion (THDv) ≤ 3 % THD (Linear Load), ≤ 5 % THD (Non-linear Load) ≤ 3 % THD (Linear Load), ≤ 4 % THD (Non-linear Load
Crest factor 3:1
Overload Sounding twice every second
BATTERIES
Battery type Depending on the applications
Numbers 2 4 6 16-20 (adjustable)
Typical recharge time 4 hours recover to 90% capacity 9 hours recover to 90% capacity
Charging current 1A/2A/4A/6A (adjustable) 1A/2A/4A/6A (adjustable, only for 6A 16 pcs batt. configuration)
Charging voltage 27.4VDC ± 1% 82.1VDC ± 1% 109.4 VDC ± 1% 273 VDC ± 1% (according to 20 battery-powered configuration)
EFFICIENCY
AC mode 88% 89% 90% 92% 93%
Battery mode 87% 88% 88% 90% 91%
Transfer time AC Mode to batt. mode Zero 0ms
Transfer time Inverter to bypass 4 ms (Typical) 0ms
Protections Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Communications RS232 (standard), USB / RS485 / dry contacts / SNMP (optional) RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation / Remote monitoring panel / MODBUS (RS485 or TCP/IP) / USB Alarm Logger / (TCP/IP) / (GSM/GPRS) Modem / Comport multiplexer (optional)
Display LCD + LED
On-Display Information Input Voltage (Source & Bypass), AC-Out Voltage, Total Load, AC-Current (Input/Output/Bypass), Charge/Discharge %, Input Frequency (Source & Bypass)
Standards EN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5,

IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1, IEC 62040-3

OTHERS
Operating temperature 0°C ~ 40°C
Storage temperature − 40°C ~ 70°C (without batteries), − 20°C ~ 40°C (with batteries)
Relative humidity 0 ~ 95% (non-condensing)
Altitude ≤ 1000 m, derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1m < 50dBA < 55dBA < 58dBA
Dimensions (H×W×D) (mm) Rackmount 88(2U)x438x310 Rackmount 88(2U)x438x410 Rackmount 88(2U)x438x530 Rackmount 133(3U)x438x580
Net weight (kg) 9 12 14 15 18
MANAGEMENT  

 

Smart RS-232/USB Supports Windows 2000/2003/XP/Vista/2008/7/8/above, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser